Fire alarm control panel features
Designed and manufactured according to EN 54-2
and EN 54-4
Compatible with Mavigard Harezmic series addressable devices
Up to 64 panels and/or repeater panels can be assembled
into a network
Extendable loops up to 16 loops, max. 2032 address capacity
for each panel
1000 user-defined zones
and 1000 event log memory
Top priority of fire alarm indication, different buttons for fire and other events, categorical classification due to events
Real time clock
Communication interrupt for fast fire alarm detection in 1.5 sec
Loop polling in 7.5 sec
4 programmable supervised remote control inputs
Protection from electromagnetic interference
Ability of communication with enhanced computers (RS232/RS485 for close access, GPRS/TCP-IP for remote control)
Supervised peripheral devices, extension cards (power supply, loop extensions, printer...)
Day and night mode, pre-alarm, contamination warning
Virtual panel, supervisor applications
Input/output modules can be connected directly to panel
Advanced control/monitoring features
Updating software on the site by the help of Boot Loader Software
Advanced parametric arrangement options for input/output devices
User-defined event types creation
|